Bently Nevada 990‑05‑70‑01‑00 Vibration Transmitter
- Supply Type
- Sample
- No
- Transport Mode
- Sea, Land, Air, Express, Others
- HS Code
Product Description
Product Details
| Brand | Bently Nevada |
| Model | 990‑05‑70‑01‑00 |
| Type | Vibration Transmitter |
| Origin | USA |
| Product Condition | New |
| Unit Price | |
| Warranty | 12 months |
The Bently Nevada 990-05-70-01-00 vibration transmitter provides a standard proportional vibration signal to equipment control systems and is intended for OEM applications involving centrifugal air compressors, small pumps, motors, fans, and other equipment. This product is a two-wire loop-powered device that accepts input from the 3300 NSv eddy-current probe and its associated extension cable (available in 5 m and 7 m system length options). The transmitter conditions the signal into an appropriate peak-to-peak vibration amplitude engineering unit and outputs this value as a proportional industrial standard signal.
✅Features
The 990-05-70-01-00 is equipped with non-isolated PROX OUT and COM terminals, as well as a coaxial connector, providing dynamic vibration signal and gap voltage outputs.
The 990-05-70-01-00 features a Test Input pin, which can be connected to a function generator for quick verification of the loop output.
Independent zero and span potentiometers are provided below the transmitter label on the 990-05-70-01-00.
The 990-05-70-01-00 channel can be configured for velocity or acceleration mode, and supports direct amplitude, 1X amplitude and phase, and 2X amplitude and phase outputs.
⚠️Important Usage Notes
- The 990-05-70-01-00 vibration transmitter is only suitable for overall machine vibration trend monitoring; compared with professional online monitoring systems, its diagnostic capabilities are limited.
- The PROX OUT dynamic signal is a non-isolated signal; when connecting AC-powered oscilloscopes, analyzers, or other equipment, it is strongly recommended to use the 990/991 test adapter to provide isolation and signal inversion.
🔌Technical Specifications
Maximum Loop Resistance: 1,000 Ω (including cable, at 35 Vdc)
Current Limit: 23 mA typical
Zero and Span: Independent external adjustments
Frequency Response: 5 Hz to 6,000 Hz, +0, -3 dB
Minimum Target Size: 9.5 mm (0.375 in) diameter
Minimum Target Size: φ9.5 mm
05 indicates the full-scale range: 0–5 mil pp (0–125 μm pp) peak-to-peak displacement.