Applications of XLPE Insulation Power Cable:
XLPE Insulation Power Cable are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Construction XLPE Insulation Power Cable
1. Conductors
The conductors shall be either of Class 1 or Class 2 of plain or metal-coated annealed copper or of plain aluminium or aluminium alloy, or of Class 5 of plain or metal-coated copper in accordance with IEC 60228.
2. Insulation
mica tape
XLPE material and thickness shall be as per IEC 60502 or BS 5467 rated for 90°C continuous operation.
3. Assembly / Inner Covering
The inner coverings may be extruded or lapped. For cables with circular cores, except cables with more than five cores, a lapped inner covering shall be permitted only if the interstices between the cores are substantially filled. A suitable binder is permitted before application of an extruded inner covering. The material is compatible with the insulating material,The materials used for inner coverings and fillers shall be suitable for the operating temperature of the cable and compatible with the insulating material.For halogen free cables, the inner covering and fillers shall also be halogen free compound.
4. Armour
Aluminum/galvanized steel/steel wires applied helically over the Inner Covering as per IEC 60502-1, or double aluminum/steel tapes and copper/tinned copper wire can also be manufactured upon request.
5. Outer Sheath
Outer sheath shall be of extruded PVC Type ST1/ST2 as per IEC 60502-1,
6. Fire Performance of Cable Sheaths
Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, Halogen Free material comply to IEC60754-1/2 and IEC 60684-2.
No.cores x cross-sec. |
Insulation thickness |
Nominal Sheath thickness |
Outer Ø approx. |
weight approx. |
Current ratings in air 30℃ |
Current ratings buried 20℃ |
|
Phase |
Neutral |
||||||
mm² |
mm |
mm |
mm |
mm |
kg / km |
A |
A |
4×4+1×2.5 |
0.7 |
0.7 |
1.8 |
14.2 |
320 |
38 |
48 |
4×6+1×4.0 |
0.7 |
0.7 |
1.8 |
15.6 |
427 |
48 |
60 |
4×10+1×6.0 |
0.7 |
0.7 |
1.8 |
18.1 |
636 |
66 |
81 |
4×16+1×10 |
0.7 |
0.7 |
1.8 |
20.8 |
941 |
88 |
107 |
4×25+1×16 |
0.9 |
0.7 |
1.8 |
24.9 |
1441 |
118 |
137 |
4×35+1×16 |
0.9 |
0.7 |
1.8 |
27.1 |
1853 |
144 |
165 |
4×50+1×25 |
1.0 |
0.9 |
1.9 |
31.6 |
2616 |
177 |
196 |
4×70+1×35 |
1.1 |
0.9 |
2.1 |
36.5 |
3578 |
227 |
244 |
4×95+1×50 |
1.1 |
1.0 |
2.2 |
41.6 |
4843 |
277 |
288 |
4×120+1×70 |
1.2 |
1.1 |
2.4 |
46.3 |
6110 |
325 |
329 |
4×150+1×70 |
1.4 |
1.1 |
2.5 |
51.2 |
7421 |
375 |
369 |
4×185+1×95 |
1.6 |
1.1 |
2.7 |
56.8 |
9191 |
433 |
418 |
4×240+1×120 |
1.7 |
1.2 |
2.9 |
63.2 |
11763 |
518 |
488 |
4×300+1×150 |
1.8 |
1.4 |
3.1 |
70.0 |
14595 |
625 |
555 |