Horizontal AHU Technical Parameters (4 Rows, 10 Fins per in
Model LG-18WA-4R
Air Flow Volume
Rated Air Flow
m3/h 18000
Air Flow Range 16.8~18.8
otor-internal linked
Pressure Pa 400
Power Input kW 2×3
Air return
Cooling Capacity kw 103.8
Heating Capacity kw 167.1
Water Flow L/min 312.9
Water Resistance Kpa 17.5
Fresh Air
Cooling Capacity kw 241.6
Heating Capacity kw 219.9
Water Flow L/min 728.5
Water Resistance Kpa 24
Noise dB(A) <68
Water inlet/outlet pipe Diameter DN 65
coil section
Copper tube 16mm
Fin space 2.6mm
Fan outlet speed 10
Coil face velocity 2.7
Heat
exchanger
size
L mm 2000
H mm 912
W 4 Rows 191.6
Weight kg 450